UL Type TC-ER Helical 600V tray cable is a high-performance cable designed for industrial control systems, power distribution, and mechanical equipment wiring. Its conductor uses 14 AWG to 10 AWG fully annealed standard bare copper, which meets the ASTM B8 Class B stranded structure. The cable insulation layer is made of cross-linked polyethylene (XLPE) and belongs to XHHW-2 type insulation. It has excellent heat resistance and is suitable for dry and humid environments at 90℃. The external 5 mil copper tape spiral shielding structure effectively improves the electromagnetic interference protection capability and ensures the stable transmission of signals and power.
Anvendelse
600V TC-ER tray cable is a multifunctional control and distribution cable suitable for a variety of industrial and commercial scenarios. It is designed for stable power supply and signal transmission in complex environments. The cable allows open installation without the need for additional protective casing, greatly simplifying the wiring cost and construction difficulty. It is rated at 600 volts and er velegnet til industrielle automatiseringssystemer, kontrolkredsløb, motorisk strømforsyning, pumpeforbindelse, belysningssystemer og mekanisk udstyrs ledninger . Kabelstrukturen vedtager høj ledningsevne, som kobberleder, XHHW -2 klasse tværbundet polyethylenisolering, spiral kobberbånd skal afdæmper og UV-resistent pvc sheath {.} it (90 grad tørt og vådt miljø), anti-interferens, oliebestandighed, fugtbestandighed, flammehæmmende, lav temperaturresistens (-40 grad kold bøjning) og andre egenskaber . Det kan bruges til kabelbakker, kabelkanaler, rørledninger eller direkte underjordisk lægning, især egnet til elektriske systemer, der kræver høj relation og langvarig betjening i barskørslinjer i barnebelægninger, eller direkte underjordisk lå Miljøer .

Certificering
TC-ER-bakkekabler er certificeret af flere myndigheder for deres sikkerhed og pålidelighed i industrielle, kommercielle og hårde miljøer . Kablerne overholder UL 1277-standarder og er anført som bakkekabel (TC), som er egnet til en række installationsmetoder, såsom kabelbakker, ledninger og jord, der lægger. på det samme tidspunkt, cablene kan være leays, ledninger, ledninger og jord, der lægger Vægge eller strukturer uden yderligere metalbeskyttelsesrør, når man opfylder specifikke fastgørelsesbehov, hvilket i høj grad forenkler installationsprocessen . kablerne passerer også UL 44 (XHHW -2) isoleringsstandard for at sikre, at de kan fungere sikkert op til 90 grad i tørre og fugtige miljøer .))

Pakke

Produktionslinie

Greater Wire er en professionel TC-er-bakke-kabelproducent, dedikeret til at tilvejebringe højtydende og højsikkerheds kabelløsninger til industriel automatisering, strømstyring og bygning af ledninger . TC-ER-kablerne, vi producerer strengt flere nordamerikanske standarder, såsom UL 1277, UL 44, UL 1581, UL 2556, IEEE 1202 og har passeret dobbeltcertifikation (TC) og udsat løb (er) . De kan bruges i vid udstrækning i kabelbakker, rørledninger, vægoverflader og direkte begravede miljøer .
Med mere end 30 års erfaring inden for tråd- og kabelfremstilling har vi avanceret produktionsudstyr og et komplet kvalitetskontrolsystem . Vi kan levere tilpassede tjenester af UL TC-ER-kabler i forskellige specifikationer i henhold regioner og har vundet ros fra kunder i ind -og udland .
kunde

Partner

FAQ
Spørgsmål: Hvad er en TCER -kabel -vurdering?
Spørgsmål: Hvad er forskellen mellem TC og TC-ER?
Spørgsmål: Kan TC-ER-kabler begraves direkte i jorden?
Populære tags: UL-type TC-er bakke kabel spiralformet 600 volt, Kina UL type TC-er bakke kabel spiralformet 600 volt producenter, leverandører, fabrik

|
Cond . størrelse
|
Dia over
Cond .
(1)
|
Insul .
Tykkelse
|
Dia over
Insul .
(2)
|
Jord
|
Jakke
Tykkelse
|
Ca. . od
(6)
|
Kobber
Vægt
|
Ca. .
Vægt
|
|
AWG
|
inches
|
inches
|
inches
|
Ingen . x AWG
|
Mils
|
inches
|
lbs ./mft
|
lbs ./mft
|
| 8 | 0.139 | 35 | 0.209 | 1x10 | 45 | 0.542 | 187 | 283 |
| 6 | 0.174 | 35 | 0.244 | 1x8 | 60 | 0.648 | 297 | 436 |
| 4 | 0.221 | 46 | 0.313 | 1x8 | 60 | 0.795 | 442 | 626 |
| 2 | 0.277 | 46 | 0.369 | 1x6 | 80 | 0.958 | 703 | 964 |
| 1 | 0.321 | 57 | 0.435 | 1x6 | 80 | 1.100 | 865 | 1192 |
| 1/0 | 0.360 | 57 | 0.474 | 1x6 | 80 | 1.184 | 1069 | 1432 |
| 2/0 | 0.404 | 57 | 0.518 | 1x6 | 80 | 1.279 | 1327 | 1732 |
| 3/0 | 0.454 | 57 | 0.568 | 1x4 | 80 | 1.387 | 1700 | 2156 |
| 4/0 | 0.510 | 57 | 0.624 | 1x4 | 80 | 1.508 | 2110 | 2624 |
| 250 | 0.558 | 68 | 0.694 | 1x4 | 80 | 1.659 | 2469 | 3076 |
| 350 | 0.661 | 68 | 0.797 | 1x3 | 110 | 1.942 | 3440 | 4272 |
| 500 | 0.789 | 68 | 0.925 | 1x2 | 110 | 2.218 | 4885 | 5888 |
| 600 | 0.866 | 79 | 1.024 | 1x2 | 110 | 2.432 | 5822 | 6994 |
| 750 | 0.968 | 79 | 1.126 | 1x2 | 110 | 2.652 | 7278 | 8602 |
|
Cond . størrelse
|
Min .
Bøjning
Radius
|
Max . træk
Spænding
|
Modstand
|
Reaktans
|
Tilladelige ampaciteter
|
|||
|
DC @ 25 grader
|
AC @ 90 grader
|
@ 60Hz
|
60 grader
|
75 grad | 90 grader | |||
| AWG | Inches |
lbs .
|
Ω/mft
|
Ω/mft
|
Ω/mft
|
Ampere
|
Ampere
|
Ampere
|
| 8 | 2.2 | 396 | 0.652 | 0.815 | 0.030 | 40 | 50 | 55 |
| 6 | 2.6 | 630 | 0.411 | 0.514 | 0.028 | 55 | 65 | 75 |
| 4 | 3.2 | 1002 | 0.258 | 0.323 | 0.029 | 70 | 85 | 95 |
| 2 | 3.8 | 1593 | 0.162 | 0.203 | 0.028 | 95 | 115 | 130 |
| 1 | 5.5 | 2009 | 0.129 | 0.162 | 0.028 | 110 | 130 | 145 |
| 1/0 | 5.9 | 2534 | 0.102 | 0.128 | 0.027 | 125 | 150 | 170 |
| 2/0 | 6.4 | 3194 | 0.081 | 0.102 | 0.027 | 145 | 175 | 195 |
| 3/0 | 6.9 | 4027 | 0.064 | 0.081 | 0.026 | 165 | 200 | 225 |
| 4/0 | 7.5 | 5078 | 0.051 | 0.064 | 0.026 | 195 | 230 | 260 |
| 250 | 8.3 | 6000 | 0.043 | 0.055 | 0.026 | 215 | 255 | 290 |
| 350 | 9.7 | 8400 | 0.031 | 0.040 | 0.026 | 260 | 310 | 350 |
| 500 | 13.3 | 12000 | 0.022 | 0.029 | 0.025 | 320 | 380 | 430 |
| 600 | 14.6 | 14400 | 0.018 | 0.025 | 0.025 | 350 | 420 | 475 |
| 750 | 15.9 | 18000 | 0.014 | 0.020 | 0.025 | 400 | 475 | 535 |