Details:
· Leder: RE: Klasse 1 massiv kobberleder RM: Klasse 2-trådet cirkulær eller cirkulært komprimeret SM: Klasse 2-trådet sektorformet
·Isolering: XLPE (Cross-Linked Polyethylene)
· Sengetøj: PVC (polyvinylklorid)
·Shed: PVC (polyvinylchlorid)
· Spændingsmærke Uo/U: 0,6/1kV
· Temperaturklassificering: Under installation -5 grader til +50 grader Fast installation: -20 grader til +90 grader
·Standarder: IEC 60502-1, Gen til VDE 0276-603, IEC/EN 60228 Flammehæmmende i henhold til IEC/EN 60332-1-2
Send Inquiry
Download
Beskrivelse
Tekniske parametre
Certificering

 

IEC 60502-1 XLPE PVC cable for industrial power distribution

PRODUKT REAL SHOT

 

IEC 60502-1 XLPE PVC cable for commercial building power supply
IEC 60502-1 XLPE PVC cable for data center power distribution
IEC 60502-1 XLPE PVC cable for BESS AC connection

IEC 60502-1 XLPE PVC cable for solar inverter AC output

Cameroun DRC 0,6/1kV kabelleverandør til entreprenører og importdistributører
Denne Cameroun og DRC side kombinerer engelsk og fransk indkøbsadfærd for kobber XLPE/PVC fast strømkabel. I produktkernen er kobberledere med XLPE-isolering og en PVC-overkappe, konfigureret som et ikke-pansret 0,6/1 kV strømkabel. Købere, der bruger sætningenfournisseur kabel cuivre XLPE PVC Douala Kinshasakan sammenligne denne nøjagtige konstruktion uden at blande den med aluminium, armeret, LSZH eller klasse 5 fleksibelt kabel. GERITEL WIRE kan udarbejde datablade, fabriksoptegnelser, inspektionsadgang og fragt-orienteret pakningsinformation. Importdistributører og entreprenører i Douala eller Kinshasa kan anmode om containere i blandet-størrelse, tosproget mærkning og projekt-for-trommelister. Fordi den ikke har nogen panser, skal kabelruten give den mekaniske beskyttelse, der kræves af installationen og lokale regler.
PRODUKTSPECIFIKATIONER

 

IEC 60502-1 XLPE PVC cable for wind farm auxiliary power

Ansøgninger

 

Disse strøm- og faste ledningskabler bruges til elforsyning i lavspændingsinstallationssystemer. De er godt tilpasset til underjordisk brug i industrielle applikationer med en ekstra mekanisk beskyttelse. Disse kabler kan fastgøres på kabelbakker, i ledninger eller fastgøres til vægge.

SPECIFIKATIONER
Spændingsmærke Uo/U 0,6/1kV
Temperaturvurdering

Under installation -5 grader til +50 grader

Fast installation: -20 grader til +90 grader

Minimum bøjningsradius Fast: 12 x samlet diameter
Leder

RE: Klasse 1 massiv kobberleder

RM: Klasse 2-trådet cirkulær eller cirkulær komprimeret

SM: Klasse 2 strandet sektorformet

Isolering XLPE (Cross-Linked Polyethylene)
Sengetøj PVC (polyvinylklorid)
Skede PVC (polyvinylklorid)
Kerneidentifikation

3 kerne: Grøn/Gul, Blå, Brun 4 kerne

4 kerner: Grøn/Gul, Brun, Sort, Grå

5 kerner: Grøn/Gul, Blå, Brun, Sort, Grå

7 kerner og derover: Sorte kerner og hvide tal

Skede farve Sort
STANDARDER IEC 60502-1, Gen til VDE 0276-603, IEC/EN 60228 Flammehæmmende i henhold til IEC/EN 60332-1-2

DIMENSIONER

INGEN. AF
KERNER

NOMINALKRYDS

SEKTIONSOMRÅDE

mm²

LEDER

TYPE

NOMINAL

TYKKELSE

AF ISOLERING

mm

NOMINAL

TYKKELSE

AF SKED

mm²

NOMINAL SAMLET

DIAMETER

mm

NOMINEL VÆGT

kg/km

1 16 RM 0.7 1.8 9.8 216
1 25 RM 0.9 1.8 11.5 318
1 35 RM 0.9 1.8 12.6 415
1 50 RM 1 1.8 14.1 543
1 70 RM 1.1 1.8 15.6 746
1 95 RM 1.1 1.8 17.6 1000
1 120 RM 1.2 1.8 19.2 1239
1 150 RM 1.4 1.8 21.2 1515
1 185 RM 1.6 1.8 23.1 1872
1 240 RM 1.7 1.8 25.8 2403
1 300 RM 1.8 1.8 2.78 2974
1 400 RM 2 1.9 31.1 3834
1 500 RM 2.2 2 34.9 4892
1 630 RM 2.8 2.8 46.6 6544
2 1.5 RE 0.7 1.8 10.1 145
2 2.5 RE 0.7 1.8 10.9 179
2 4 RE 0.7 1.8 11.8 226
2 6 RE 0.7 1.8 12.8 284
2 6 RM 0.7 1.8 13.1 295
2 10 RM 0.7 1.8 15 416
2 16 RM 0.7 1.8 17 581
2 25 RM 0.9 1.8 20.4 859
2 35 RM 0.9 1.8 22.5 1109
3 1.5 RE 0.7 1.8 10.5 162
3 2.5 RE 0.7 1.8 11.4 205
3 4 RE 0.7 1.8 12.4 265
3 6 RE 0.7 1.8 13.4 338
3 10 RM 0.7 1.8 15.8 505
3 16 RM 0.7 1.8 18 719
3 25 RM 0.9 1.8 21.6 1072
3 35 RM 0.9 1.8 23.9 1403
3 50 SM 1 1.9 23.8 1581
3 16/10 SM 0.7 1.8 19.8 875.5
3 25/16 SM 0.9/0.7 1.8 22.4 1223
3 35/16 SM 0.9/0.7 1.8 24.3 1557
3 50/25 SM 1/0.9 1.9 26.9 1863
3 70/35 SM 1.1/0.9 2 30 2594
3 95/50 SM 1.1/1 2.2 33.8 3505
3 120/70 SM 1.2/1.1 2.3 37 4440
3 150/70 SM 1.4/1.1 2.4 41.6 5333
3 185/95 SM 1.6/1.1 2.6 45.8 6701
3 240/120 SM 1.7/1.2 2.8 51.6 8674
3 300/150 SM 1.8/1.4 3 67.2 10624
4 1.5 RE 0.7 1.8 11.3 188
4 2.5 RE 0.7 1.8 12.2 240
4 4 RE 0.7 1.8 13.3 314
4 6 RE 0.7 1.8 14.5 408
4 10 RE 0.7 1.8 17.1 615
4 16 RE 0.7 1.8 19.6 885
4 25 RE 0.9 1.8 23.7 1330
4 35 RE 0.9 1.8 26.2 1758
4 50 SM 1 2 27.1 2082
4 70 SM 1.1 2.1 31.4 2937
4 95 SM 1.1 2.2 35 3955
4 120 SM 1.2 2.4 39.3 4979
4 150 SM 1.4 2.6 43.6 6129
4 185 SM 1.6 2.7 48 7591
4 240 SM 1.7 2.9 53.9 9875
4 300 SM 1.8 2.6 68.9 15124
5 1.5 RE 0.7 1.8 12.1 218
5 2.5 RE 0.7 1.8 13.1 281
5 4 RE 0.7 1.8 14.3 372
5 6 RE 0.7 1.8 15.6 486
5 10 RM 0.7 1.8 18.6 740
5 16 RM 0.7 1.8 21.3 1071
5 25 RM 0.9 1.8 25.9 1619
5 35 RM 0.9 1.8 28.8 2138
5 50 RM 1 2.1 29.4 2578
5 70 RM 1.1 2.2 33.7 3616
5 95 RM 1.1 2.4 38.6 4933
5 120 RM 1.2 2.5 42.6 6153
5 150 RM 1.4 2.7 47.7 7587
5 185 RM 1.6 2.9 52.8 9454
5 240 RM 1.7 3.1 58.7 12242
7 1.5 RE 0.7 1.8 12.9 260
7 2.5 RE 0.7 1.8 14 342
7 4 RE 0.7 1.8 15.4 461
10 1.5 RE 0.7 1.8 15.6 357
10 2.5 RE 0.7 1.8 17.2 475
10 4 RE 0.7 1.8 19 646
12 1.5 RE 0.7 1.8 16.1 394
12 2.5 RE 0.7 1.8 17.6 528
14 1.5 RE 0.7 1.8 16.8 436
14 2.5 RE 0.7 1.8 18.5 592
16 4 RM 0.7 1.8 23 971
19 1.5 RE 0.7 1.8 18.4 543
19 2.5 RE 0.7 1.8 20.3 746
24 1.5 RE 0.7 1.8 21.2 675
24 2.5 RE 0.7 1.8 23.4 931
30 1.5 RE 0.7 1.8 22.3 788
30 2.5 RM 0.7 1.8 26.3 7764
40 1.5 RE 0.7 1.8 24.6 995
40 2.5 RE 0.7 1.9 27.5 1416

LEDERE

Klasse 1 solide ledere til enkelt--kerne- og multi-lederkabler

NOMINALT KRYDS

EKTIONSOMRÅDE

mm²

MAKSIMAL MODSTAND AF LEDEREN VED 20 grader

ohm/km

Cirkulære, udglødede kobberledere
Almindelig
0.5 36
0.75 24.5
1 18.1
1.5 12.1
2.5 7.41
4 4.61
6 3.08

 

Klasse 2-strengede ledere til enkelt-kerne- og multi-lederkabler

NOMINELLT KRYS

AFSNITAL OMRÅDE

mm²

MINIMUM NR. AF LEDNINGER I LEDEREN

MAKSIMAL MODSTAND AF LEDEREN VED 20 grader

ohm/km

Cirkulær Cirkulær komprimeret Udglødede kobberledere
Cu Cu Almindelige ledninger
4 7 6 4.51
6 7 6 3.08
10 7 6 1.83
16 7 6 1.15
25 7 6 0.727
35 7 6 0.524
50 19 6 0.387
70 19 12 0.268
95 19 15 0.193
120 37 18 0.153
150 37 18 0.124
185 37 30 0.0991
240 37 34 0.0754
300 61 34 0.0601
400 61 53 0.0470
500 61 53 0.0366

ELEKTRISKE EGENSKABER

Nuværende bæreevne ved 30 grader

NOMINELLT KRYS

SEKTIONSOMRÅDE

mm²

ENKEL KERNE

2-40 CORE

ampere

I Jorden I luften I Jorden I luften
Flad Trefoil Flad Trefoil
1.5 - - - - 31 24
2.5 - - - - 40 32
4 82 54 57 44 52 42
6 102 67 72 56 64 53
10 136 89 99 77 86 74
16 176 115 131 102 112 98
25 229 148 177 138 145 133
35 275 177 217 170 174 162
50 326 209 265 207 206 197
70 400 256 336 263 254 250
95 480 307 415 325 305 308
120 548 349 485 380 348 359
150 616 393 557 437 392 412
185 698 445 646 507 444 475
240 815 517 774 604 517 564
300 927 663 901 697 585 649
400 1064 749 1060 811 - -
500 1227 843 1252 940 - -

DE-RATINGSFAKTORER

Til andre jordtemperaturer end 20 grader

LUFTTEMPERATUR 10gradC 15 grader 20 grader 25 grader 30 grader 35 grader 40 grader 45 grader 50 grader
DE-RATING FAKTOR 1.07 1.04 1.00 0.96 0.93 0.89 0.85 0.80 0.76

 

For andre lufttemperaturer end 30 grader

LUFTTEMPERATUR 20 grader 25 grader 30 grader 35 grader 40 grader 45 grader 50 grader 55 grader 60 grader
DE-RATING FAKTOR 1.08 1.04 1.00 0.96 0.91 0.87 0.82 0.76 0.71
CERTIFIKATIONER

 

IEC 60502-1 XLPE PVC cable for EV charging feeder

EMBALLAGE

 

IEC 60502-1 XLPE PVC cable for factory electrical installation

Rulle

IEC 60502-1 XLPE PVC cable for water treatment plant

Lille træhjul

IEC 60502-1 XLPE PVC cable for mining power distribution

Stål træhjul

ANVENDELSE

 

IEC 60502-1 XLPE PVC cable for oil and gas facility
Høj-kommerciel bygnings hovedstrømdistribution
IEC 60502-1 XLPE PVC cable for generator connection
Industrielt anlæg Lav-strømdistribution
IEC 60502-1 XLPE PVC cable for motor and pump feeder

Kommunal Vandbehandling og Pumpestation Strømforsyning

 

CASE

 

IEC 60502-1 XLPE PVC cable for switchgear connection

Babanusa-Adila Power Transmission Project

IEC 60502-1 XLPE PVC cable for substation auxiliary power

Italiens eltestprojekt

IEC 60502-1 XLPE PVC cable for utility distribution network

Oyu Tolgoi kobbermineprojekt

HVORFOR VÆLGE OS

 

30Års erfaring
i én{0}}et-stop-tjeneste

Dongguan Greater Wire & Cable Co., Ltd. er en professionel kabelproducent i-kvalitet i Kina, der leverer certificerede elektriske kabelløsninger til bygge-, industri-, minedrifts-, energi- og infrastrukturprojekter verden over.

Med en 30.000 m² fabrik, 30 produktionslinjer, erfarne ingeniører og et strengt kvalitetskontrolteam leverer vi pålidelige, sporbare og kompatible kabelprodukter til internationale ingeniørapplikationer. Vores produkter understøttes af certificeringer, herunder SAA, UL, cUL, VDE, TÜV, CE, CB, IEC, BPS og ISO.

Vi er forpligtet til sikkerhed, kvalitet, gennemsigtighed og langsigtet-partnerskab. Fra råmaterialeinspektion til test af færdige produkter er hver batch omhyggeligt kontrolleret for at sikre stabil ydeevne og pålidelig projektanvendelse.

Større kabel - certificeret kvalitet. Pålidelig forsyning. Engineering værdi.

IEC 60502-1 XLPE PVC cable for cable tray installation
 
15K
Afsluttede projekter
150+
professionelt personale
15K
glade kunder
92+
priser og certifikater
ANLÆGSUDSTYR

 

IEC 60502-1 XLPE PVC cable for underground cable duct
 
IEC 60502-1 XLPE PVC cable for infrastructure project
 
IEC 60502-1 XLPE PVC cable for modular building power distribution
 
Cu XLPE PVC cable 4x50mm2 0.6/1kV
 
N2XY cable 4x50mm2 0.6/1kV
 
Cu XLPE PVC cable 4x70mm2 0.6/1kV
 
GLOBALE CERTIFIKATIONER

 

N2XY cable 4x70mm2 0.6/1kV

KUNDEFOTOS
 

Cu XLPE PVC cable 4x95mm2 0.6/1kV

INTERNATIONAL TRANSPORT

 

01

Søfragt

Vi tilbyder pålidelige søfragtløsninger til store-volumenordrer. Dine varer er sikkert pakket og afsendt i containere, hvilket sikrer omkostningseffektiv-levering til havne over hele verden.

02

Luftfragt

For hurtigere levering sikrer vores luftfragtservice, at dine produkter hurtigt når internationale destinationer med omhyggelig håndtering og fuld sporing undervejs.

03

International Express

Har du brug for hasteforsendelser? Vores internationale ekspresservice leverer små til mellemstore ordrer effektivt og giver dør-til-dørservice med sporing i realtid- for ro i sindet.

N2XY cable 4x95mm2 0.6/1kV
SAMARBEJDSPARTNER

 

Vi søger en samarbejdspartner til at udvide vores forretning.

Cu XLPE PVC cable 4x120mm2 0.6/1kV
N2XY cable 4x120mm2 0.6/1kV
Cu XLPE PVC cable 4x150mm2 0.6/1kV
N2XY cable 4x150mm2 0.6/1kV
Cu XLPE PVC cable 4x185mm2 0.6/1kV
N2XY cable 4x185mm2 0.6/1kV
Cu XLPE PVC cable 4x240mm2 0.6/1kV
N2XY cable 4x240mm2 0.6/1kV
Cu XLPE PVC cable 4x300mm2 0.6/1kV
N2XY cable 4x300mm2 0.6/1kV
Hvordan samarbejder man med os?

Del blot dine krav, modtag vores professionelle løsning, bekræft prøver, og nyd hurtig, pålidelig produktion og verdensomspændende levering - at arbejde med os er så nemt.

Vores adresse

Bygning 2, No. 40 Luxi 2nd Road, Liaobu Town, Dongguan City, Guangdong-provinsen, Kina

Telefonnummer

+86 136 6257 9592

+86 135 1078 4550

E-mail

manager01@greaterwire.com

Cu XLPE PVC cable 5x4mm2 0.6/1kV
FAQ

 

Har enkelt-kabler brug for specielle klamper?
Når kunder spørger om valg af enkeltleder kabelklemmer, er det praktiske svar: Klipper skal modstå kabelvægt og elektromekaniske kræfter under en fejl. Materiale, afstand, trekløver eller fladt arrangement og kort-kredsløbsniveau bør koordineres. GERITEL WIRE kan organisere batchsporbarhed, testdokumentation og forsendelsesidentifikation til projektforsyning. Angiv systemspænding, belastning, rutelængde, installationsmetode og påkrævede dokumenter til valgstøtte.
Skal tre enkelt-fasekabler installeres i trefoil?
Trefoil kan give et kompakt og magnetisk afbalanceret arrangement, men ampacitet, klaffekræfter, varmeafledning og termineringsgeometri skal kontrolleres mod flade formationsalternativer. GERITEL WIRE behandler trefoil-enkeltleder-strømkabelinstallation som et-projektspecifikt krav, ikke som en etiket-kun erstatning. GERITEL WIRE hjælper distributører med at sammenligne det ønskede modelnavn med den faktiske Cu/XLPE/PVC-konstruktion. Det endelige valg skal følge det godkendte datablad, lokale forskrifter og installationsdesign.
Kan AC-kabler med enkelt-kerne køre separat gennem stålrør?
For enkeltlederkabel i stålrør: Adskillelse af faseledere gennem individuelle ferromagnetiske kapslinger kan forårsage opvarmning fra magnetisk flux. Alle ledere i kredsløbet skal arrangeres i overensstemmelse med de gældende ledningsregler og teknisk design. GERITEL WIRE kan koordinere tredjeparts-inspektion, når omfanget og tidspunktet er aftalt i indkøbsordren. Angiv eventuelle CPR-, flamme-, UV-, vand- eller mekaniske krav separat i forespørgslen.
Hvilken type kabelforskruning skal bruges til ikke-pansret kabel?
Brug en forskruning, der er dimensioneret til den faktiske udvendige diameter og egnet til skabets krav til indtrængning, miljø og fastholdelse. Der kræves ingen panserklemmekomponent til denne konstruktion. En pålideligvalg af ikke-pansret strømkabelforskruningbeslutning kræver derfor et godkendt konstruktions- og installationsgrundlag. GERITEL WIRE understøtter projektordrer i blandet-størrelse med kabel-plangennemgang og praktisk eksporttromleallokering. Bekræft lederklasse, kernefarver, tromlængder og inspektionsomfang før produktion.

 